Multipurpose module MPM
MPM is a multi purpose module designed for automated controlling and monitoring. It is also used for general communication tasks at RS485 and RS232 lines.
MPM exists in several modifications. These modifications solve autonomous automatic control and monitoring of different technologies. Modules with different software modifications interfere with several types of sensors and communicate with subordinate systems. Modules work completely autonomously and its controlling algorithm could be parameterized by a connected surveillance computer and infield single purpose device - tester
MPM can be also fully configured by a user of a notebook, equipped with designated software and RS232 serial line or Ethernet.
MPM autonomously runs battery backed real time clock with day-light saving time calendar. MPM is equipped with 10 Base-T Ethernet, three ports EIA/TIA 485 and three ports EIA/TIA 232. Communication ports can be divided in two groups. Ports communicating with superiority systems (eg. surveillance remote computer) and ports communicating with subordinate modules (eg. farcom 8DI8DO modules). There are 19200/9600 baudrates designated for master systems and 9600/4800 bps for connection of slave systems. The supported communication protocol is MODBUS ASCII. MPM also contains 2 digital inputs and 2 digital outputs
MPM is fully independent of the supervisory communication. There is also a possibility to use the device in locations where there is no supervisory system. In this situation is the module configured by the tester or by a portable computer.
SPECIFICATION
| Supply voltage | 12-33V DC 9-24V AC |
| Power input | 3W at 24VDC |
| Baud rate | 300÷19200 Bauds (see the module description) |
| Inputs/Outputs | 3x RS 232 2x EIA/TIA 485 1x IEE 802.3 10 Base-T Ethernet (VSP) 2x isolated log. input 12-36V DC 2x isolated contact max 100V/1A AC, 120V/0,3V DC |
| Local terminal | LED diodes, test terminal connection port |
| Environmental protection | IP20 |
| Mechanical design | Case with DIN rail 35mm mounting |
| Dimension | 48 x 101 x 121mm3 (w x h x d) |
| Environmental conditions | operating temperature range : -20°C až +70°C storage temperature range: -40°C až +80°C relative humidity: do 80%, % no condensing |
| Case material | ABS, lead PC |
| Dielectric strength |
supply to EIA/TIA232 1,5kV DC, inputs EIA/TIA232, EIA/TIA 485 1,6kV RMS |
| Připojovací svorkovnice | řada WAGO 231 |
There are following modifications of the multipurpose module :
- MPM-R (Railheat) - switch point heating control
- MPM-L (Light) - lights control
- MPM-H (Heat) - building heating control
- MPM-S (Switch) - special communication purposes
MPM-R
MPM-R evaluates digital temperature sensors, rainfall sensors and snowdrift sensors. According to this information it controls the heating of rail switch points. It contains separate controlling algorithms for switch rod and switch point heating.
Maximální konfigurace:- 12 switch-points rails
- 12 switch-points rods
- 4 8DI/8DO modules
- 6 CVS-E modules
- 2 temperatures TE/MB modules
- 2 falls sensors W SENSOR
Example of parameters in settings window:
MPM-L
The purpose of MPM-L is to control lights and lightings. It evaluates information from
- sun relay
- astronomical calendar with sunrise and sunset times
- special calendar of the Czech Railway
- time schedule
- external inputs (e.g. information about an aproaching train )
It is possible to configure several regimes and combinations of mentioned features.
Maximal configurations
- 20 lighting outputs
- 1 sun relay nebo digital luxmeter LX-2
- 4 8DI/8DO modules
- 6 CVS-E modules
Example of parameters in settings window:
MPM-H
MPM-H controls electrical heating of buildings according to information from indoor and outdoor temperatures sensors, thermostats and according to schedule set.
Some implemented functions:
- Heating limitation by external temperature - heating will be stopped, when outdoor temperature reaches set limit.
- Stop of heating in high-price tariff
- Local control - allows users to change desired temperature be means of local controlling equipment - terminal
- Local control restriction -an administrator of the module could restrict previous module function
Maximal configuration
- 16 heating outputs
- 4 8DI/8DO modules
- 6 CVS-E modules
- 16 temperature modules (it is possible to share temperatures modules among several controlled circuits)
Example of parameters in settings window:
MPM-S