Current and Voltage Sensor - CVS

CVS is a device designed for checking of currents and voltages, measured in controlled electrical circuits. It consists of CVS-M (Measurement) module and CVS-E (Evaluation) module. A ground-shielded 37 wires cable terminated by CANON connectors connects these modules together.

plná velikosti

Wires of measured circuits are led through current transformers placed on CVS-M module. The CVS-E module is usually connected by a modbus RS485 line to the master module MPM. MPM module then evaluates information about the measured circuits and reports failures.

CVS is both hardware and software configured. There are switches to set the communication parameters and modbus address. Connected software than configures the range of measured current, saves correct values of power load to a non-volatile memory.

plná velikosti

The device evaluates both the current and the voltage, which is the reason, why a calibration assignment of measured voltage phase to every transformer is necessary. Information about actual state and measured values can be read by means of a modbus RS485 line.

In FARCOM system is the CVS module usually put on the subsidiary RS485 line, which is mastered by a MPM module. There can be connected up to 6 CVS-E modules to one MPM module. One CVS-E is prepared to control 12 currents with 3 different voltages.

SPECIFICATION

Supply voltage 12-33V DC
9-24V AC
Power input max. 1W at 24VDC
Baud rate 300÷19200 Bauds
Input Voltage 3 x voltage inputs 230÷400V RMS(CVS M)
Input Current 1. range 0÷6A RMS
2. range 0÷30A RMS
(can be configured on every single input)
Environmental protection IP20
Mechanical design case with DIN rail 35mm mounting
Dimensions 22,5 x 101 x 121mm3 (w x h x d) – CVS-E
160 x 90 x 58mm3 (w x hx d) – CVS-M
Environmental conditions operating temp. range: -20°C - +70°C
storage temp. range : -40°C - +80°C
relative humidity : do 80%, non condensing
Case material ABS + PC lead CVS-E
Noryl CVS-M
Dielectric strength supply/inputs 3,75kV RMS
supply/line EIA/TIA 485 - no isolation
Connector WAGO 231